ex. VAT, ex. delivery costs
1 x tube for use with PCE-series pressure metersEach tube is 1 m long, with an inner diameter of 5 mm and an outer diameter of 9 mm
PCE-PDA 1L Manometer for relative and differential pressure / Pitot tube adaptable to pressure gauge / MAX MIN function / Data logger
The differential pressure gauges of the PCE-PDA series are reliable differential pressure gauges for pressure measurement of gasses in the range of ± 200 Pa, ± 2kPa and 20 kPa depending on the model. The differential pressure gauge has many different pressure measuring functions. This gives the user more than 16 units. Furthermore, the differential pressure gauge measures in addition to the differential pressure, the temperature, flow velocity and volume flow. In addition, the maximum and minimum differential pressure can be displayed in the two-part graphic display. The resolution of the differential pressure can optionally be switched. The differential pressure gauge incorporates a high-precision mode that increases the resolution tenfold.
The PCE-PDA differential pressure gauge has a data logger function. This makes it possible to carry out a leak test on pressure lines in addition to the continuous storage of the measured values. In the data logger mode, it is possible to set the differential pressure gauge to a duration in which the data is stored at a previously selected interval. In the leakage measurement mode, the user must specify the measurement duration and the differential pressure level. After the measurement, the differential pressure gauge then displays the deviation from the set point. In addition to these two functions, the differential pressure gauge, with optional Pilot tubes, can determine the flow velocity or volume flow in pipes.
Measuring range temperature | 0 ... 50°C / 32 ... 122°F |
Resolution | 0.1°C / 0.2°F |
Accuracy | ± 1°C / 2°F |
Measuring range pressure | ± 2 kPa |
Resolution | 0.1 / 1 Pa |
Accuracy | ± 0.5% of final value |
Nominal pressure | 2 kPa |
Overpressure | 10 kPa |
Burst pressure | 100 kPa |
Media | Liquids / air |
Measuring rate | 10 Hz |
Measurement units | Pa, hPa, kPa, MPa, mbar, bar, ATM, kg / cm², mmH2O, cmH2O, inH2O, mmHg, inHg, Torr, PSI, PSF |
Pressure | Differential Pressure relative pressure (if neg. Pressure connection open) |
Pressure connections | 5 mm nipple for quick connectors |
Max, Min and Hold function | Yes |
Data logger | 1024 memory slots 1 s ... 255 h Recording time per memory location 1 s ... 24h recording interval |
Medium | For air and non-explosive gasses |
Zero correction | Yes, with a zero key |
Averaging | Yes, between 0.1 ... 9.9 s |
Display | Graphic LCD with backlight |
Protection | IP41 |
Power supply | 2 x 1.5V AA battery / 1.2V NiMh battery 5V / 500-mA USB power adapter |
Current consumption | 50-mA (with backlight) 10-mA (without backlight) |
Operating temperature | 0 ... 50°C / 32 ... 122°F |
Storage temperature | 10 ... 55°C / 50 ... 131°F |
Dimensions | 145 x 85 x 35 mm / 5.7 x 3.3 x 1.4 in |
Weight | About 285 g / < 1 lb |
ex. VAT, ex. delivery costs
SR-305 is a pitot tube used to determine the directional airflow velocity in ventilation ducts using differential pressure. Suitable for the measurement of dynamic pressure of gaseous media in flow-restricted line sections. Prandtl tube (i.e., pitot-static tube) with elliptical head shape for high accuracy.
ex. VAT, ex. delivery costs
SR-483 is a pitot tube used to determine the directional airflow velocity in ventilation ducts using differential pressure. Suitable for the measurement of dynamic pressure of gaseous media in flow-restricted line sections. Prandtl tube (i.e., pitot-static tube) with elliptical head shape for high accuracy.
ex. VAT, ex. delivery costs
SR-795 is a pitot tube used to determine the directional airflow velocity in ventilation ducts using differential pressure. Suitable for the measurement of dynamic pressure of gaseous media in flow-restricted line sections. Prandtl tube (i.e., pitot-static tube) with elliptical head shape for high accuracy.
ex. VAT, ex. delivery costs
Certificate, e.g. for compliance with your DIN ISO 9000. For this purpose, we send the pressure gauge to an independent calibration laboratory. The measured values, the serial number and you as the client are recorded on this ISO certificate.