The Insulation Tester / Insulation Meter PCE-IT100 measures insulation resistances with auxiliary voltages of 125V, 250V, 500V and 1000V, up to a maximum of 4000 MΩ. Furthermore, the measurement of low resistances up to 400 Ω and a measurement function for alternating and DC voltages are offered by this Insulation Tester / Insulation Meter. A continuity tester with a beep is also part of the equipment of the insulation meter. In addition to a data-hold function for holding the current measured value, the max. or min. value in the Insulation Tester / Insulation Meter can also be recorded during voltage and low-ohm measurement.
Thanks to the large numbers and the lighting, the display of the Insulation Tester / Insulation Meter is easy to read even under difficult lighting conditions. The large buttons and the rotary knob for selecting the measuring functions allow easy operation of the PCE-IT 100 insulation meter. The Insulation Tester / Insulation Meter comes with a set of test leads with test probes, a test lead with crocodile clip and 6 batteries.
- For new plants (dry rooms): 1000 ohms x volts of operating voltage (e.g. at 230 volts > 230 kOhms)
- For new installations (wet rooms, outdoors): 500 ohms x volts of operating voltage
- Earthed devices: 1000 ohms x volts of operating voltage
- Protected devices: 2 MOhm
- Power tools: 2 MOhm
- Protective extra-low voltage: 250 kOhm
- Electrical measuring devices: 5 MOhm
- Common test voltage values are 100 volts for low-voltage and telecommunication systems, 500 volts for building installations and home appliances, and 1000 volts for low-voltage motors and transformers
| Direct voltage DC | |
| Measuring range | 0 ... 1000 V |
| Resolution | 1 V |
| Accuracy | ±(0.8% 3 Digits) |
| Overload | 1000 V rms |
| AC voltage | |
| Measuring range | 0 ... 750 V |
| Resolution | 1 V |
| Accuracy | ±1.2% ±10 Digits |
| Overload | 750 V rms |
| Frequency range | 40 ... 400 Hz |
| Insulation resistance | |
| Test voltage DC | 125V |
| Measuring range | 0,125 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) |
| Insulation resistance | |
| Test voltage DC | 250V |
| Measuring range | 0,25 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) M Ω |
| Insulation resistance | |
| Test voltage DC | 500V |
| Measuring range | 0,5 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) |
| Insulation resistance | |
| Test voltage DC | 1000V |
| Measuring range | 1 ... 4000 M Ω |
| Resolution | 0,01 M Ω |
| Accuracy | ±(3% +10 Digits) |
| Resistance | |
| Measuring range | 0 ... 40 Ω |
| Resolution | 0,01 Ω |
| Accuracy | ±1.2% ±3 digits |
| Resistance | |
| Measuring range | 0 ... 400 Ω |
| Resolution | 0,1 Ω |
| Accuracy | ±1.2% ±3 digits |
| General technical data | |
| Measuring functions | MIN, MAX, HOLD |
| Measuring rate | 0,4 Hz |
| Automatic power-off | 10 min |
| Operating height | 2000 m max. above sea level |
| Test current | ≤ 200 mA |
| Fuse(s) | 10 A / 600V (5 x 20 mm) |
| Menu language | English, English (GB) |
| Protection class (device) | IP20 |
| (Rechargeable) battery | 6 x 1,5 V AA battery , Alkali-manganese |
| Capacity | 3000 mAh |
| Operating conditions | 0 ... 40 °C , 0 ... 80 % RH |
| Storage conditions | -10 ... 60 °C , 0 ... 70 % RH |
| Dimensions ( L x W x H ) | 200 x 92 x 50 mm |