Order no.: PCE-VA 20-SET

Environmental Meter with Capture Hoods PCE-VA 20-SET


£ 410.00
£ 492.00
:
4250348714664
PCE-VA 20-SET
price ex. (VAT / delivery)
Delivery time: 1-2 working days

Description

Environmental Meter PCE-VA 20-SET with Capture Hoods
Combination anemometer-hygrometer-thermometer for HVAC system balancing

PCE-VA 20-SET is a environmental meter with capture hoods for assessing and balancing heating, ventilation and air conditioning or cooling (HVAC) systems. In addition to measuring air flow velocity (i.e., wind speed), this environmental meter measures volume flow, relative humidity (RH), air temperature, dew point temperature and wet-bulb temperature. This environmental meter features a 10 cm / 3.9" Ø fan impeller, easy-to-read backlit LCD, and functions such as display hold, average value, maximum value, minimum value, battery-saving automatic power off, low-battery indicator, and metric or imperial unit selection.


Highlights

- Measures air flow velocity, volume flow, relative humidity, air temperature, dew point temperature and wet
  bulb temperature
- Air flow velocity range: 0.2 ... 30 m/s (39.4 ... 5905.5 fpm)
- Accuracy: ±(1.5% of measured value + 0.3 m/s) when less than 20 m/s, ±(3% of measured value + 0.3
  m/s) when more than 20 m/s
- Resolution: 0.1
- Includes 2 x flow hoods (1 x round 210 mm / 8.3" Ø, 1 x square 346 x 346 mm / 13.6 x 13.6 in)
- 10 cm / 3.9 in Ø fan impeller
- Easy-to-read backlit LCD
- Display hold, average value, maximum value, minimum value, battery-saving automatic power off, low
  battery indicator, and metric or imperial unit selection functions


Specification

Technical Specification
Air flow velocity measuring range
0.2 ... 30 m/s (39.4 ... 5905.5 fpm)
Air flow velocity accuracy <20 m/s: ±(1.5% of rdg. + 0.3 m/s)
>20 m/s: ±(3% of rdg. + 0.3 m/s)
Air temperature measuring range -20 ... 60 °C / -4 ... 140 °F
Air temperature accuracy ±0.6 °C
Air temperature resolution 0.1 °C / °F
Humidity measuring range 0.1 ... 99.9 % r.H.
Humidity accuracy ±3 % r.H. (at 25 °C / 77 °F and 10...90 % r.H.)
else: ±5 % r.H.
Humidity resolution 0.1 % r.H.
Temperature response time 60 seconds
Humidity response time 60 seconds
LCD update 1 x per second
Wet bulb temperature display -20 ... +59.9 °C / -4 ... 139.8°F
Dew point temperature display -5 ... +59.9 °C / 23 ... 139.8°F
Volume flow display 0 ... 99999 m³/min
Volume flow resolution 0.1 m³/min (0...9999,9 m³/min)
1 m³/min (10000...99999 m³/min)
Automatic shutdown after 20 minutes of inactivity
LCD size 32.5 x 54 mm / 1.28 x 2.13" (H x W)
Power supply 4 x 1.5 V AAA batteries
Operating conditions 0 ... +50 °C / 32 ... 89.6°F, <80 % r.H.
Storage conditions -10 ... +50 °C / 14 ... 89.6°F, <90 % r.H.
Dimensions 269 x 106 x 51 mm / 10.6 x 4.1 x 2.0"
Weight ca. 200 g / 7 oz

Delivery Scope

1 x Environmental Meter (PCE-VA 20)
1 x Square capture hood (AFC-PCE-VA)
1 x Round capture hood (AFC-PCE-VA)
4 x AAA batteries
1 x User manual
1 x Carrying case