Order no.: PCE-DC 20

HVAC Meter PCE-DC 20

US$ 197.00
:
4250348720559
PCE-DC 20
ex. VAT, ex. delivery costs
Available in: 1-2 days

Description

HVAC meter PCE-DC 20
AC / DC digital multimeter with direct frequency measurement on the clamp / LCD display / Automatic shutdown when not in use / Current measurement up to 1000 A / For mobile use / Current clamp opening 40 mm (1.6 in)

The digital multimeter is a versatile measuring instrument for the determination of currents, voltages and many other electrical quantities. With a current clamp opening of 40 mm / 1.6 in, even cables with a larger diameter can be tested with the digital multimeter. Thus, with the digital multimeter, current measurements of up to 1000 A AC / DC are possible. 

The user can perform frequency measurements with this digital multimeter. This ensures contactless frequency measurement with the digital multimeter. Thus, the digital multimeter is a useful addition to the equipment of an electrician.

Highlights

- Current clamp opening 40 mm / 1.6 in
- Backlit LCD display
- Automatic shutdown
- Ready for operation after switching on
- Extensive measuring functions
- Measuring range is selected automatically

Specification

DC  power  
measuring range Resolution Accuracy
400 A 0.1 A ± 3% + 5 digits
600 A 1 A
± 3% + 5 digits
1000 A 1 A ± 3% + 6 digits
     
Overvoltage protection: 120% of the measuring range for a maximum of 60 seconds
       

 
AC  power  
measuring range Resolution Accuracy
400 A 0.1 A ± 3% + 5 digits
600 A 1 A ± 3% + 5 digits
1000 A 1 A ± 3% + 6 digits
     
Frequency range: 50 ... 60 Hz
Overvoltage protection: 120% of the measuring range for a maximum of 60 seconds
   

 
DC voltage  
measuring range Resolution Accuracy
4V 1 mV ± 0.5% + 5 digits
40V 10 mV ± 0.5% + 5 digits
400V 0.1V ± 0.5% + 5 digits
600V 1V ± 1% + 5 digits
1000V 1V ± 1% + 5 digits
     
Input impedance: 10 MΩ
Overvoltage protection: 1000V DC or 700V AC RMS
     

 
AC voltage  
measuring range Resolution Accuracy
4V 1 mV ± 1.2% + 5 digits
40V 10 mV ± 1.2% + 5 digits
400V 0.1V ± 1.2% + 5 digits
600V 1V ± 2% + 5 digits
1000V 1V ± 2% + 5 digits
     
Input impedance: 10 MΩ
Overvoltage protection: 1000V DC or 700V AC RMS
Frequency range: 40 ... 400 Hz
 

 
Resistance  
measuring range Resolution Accuracy
400 Ω 0.1 Ω ± 1% + 5 digits
4 kΩ 1 Ω ± 1% + 5 digits
40 kΩ 10 Ω ± 1% + 5 digits
400 kΩ 0.1 kΩ ± 1% + 5 digits
4 MΩ 1 kΩ ± 1% + 5 digits
40 MΩ 10 kΩ ± 2% + 5 digits
     
Overvoltage protection: 250V AC / DC RMS
     

 
Frequency (direct)  
measuring range Resolution Accuracy
40 Hz 1 Hz ± 0.1% + 1 digits
400 Hz 1 Hz ± 0.1% + 1 digits
4 kHz 10 Hz ± 0.1% + 1 digits
40 kHz 100 Hz ± 0.1% + 1 digits
100 kHz 100 Hz ± 0.1% + 1 digits
     
Measuring range: 1 ... 10V RMS, 40 Hz ... 100 kHz
 

 
Frequency (current clamp)  
measuring range Resolution Accuracy
40 Hz 0.01 Hz ± 0.1% + 1 digits
400 Hz 0.1 Hz ± 0.1% + 1 digits
     
Frequency range: 40 ... 400 Hz (> 20 A)
   
Further measuring functions  
Continuity test Beep at < 40 Ω
Diode test Indicates the forward voltage
   
General specifications  
Measuring rate 2 ... 3 measurements per second
Display LCD 3999 digits
Measuring range selection Automatically
Automatic shutdown After 30 minutes non-use, deactivatable
Maximum forceps opening 40 mm / 1.6 in
Coefficients 0.1 x accuracy x °C / °F*
Maximum voltage 1000V CAT II, ​​600V CAT III
Maximum working height 2000 m / 6561 ft
Operating conditions
5 ... 35°C, < 75% rh
Storage conditions -10 ... 35°C, < 75% rh
Power supply 3 x 1.5V AAA batteries
Dimensions 225 x 86 x 32 mm / 8.9 x 3.4 x 1.3 in
Weight About 330 g / < 1 lb
   
Accuracies are given at ambient conditions of 18 ... 28°C, 65 ... 83°F.
*The temperature is the difference between the temperature of the operating conditions and the current ambient temperature.
 
Example:
Is the current ambient temperature greater than the temperature of the operating conditions
(50°C / 122°F (current ambient temperature)) - (40°C / 104°F (operating temperature)) = 10°C / 50°F
Is the current ambient temperature less than the temperature of the operating conditions
(0°C / 32°F (operating temperature)) - (-5°C / 23°F (current ambient temperature)) = 5°C / 41°F
 

Delivery Scope

1 x HVAC meter PCE-DC 20
1 x Pair of test leads
3 x 1.5V AAA batteries
1 x Transport bag
1 x User manual

Downloads