| Technical specifications | |
| Sensor type | electrochemical |
| Housing | housing connection box: carbon-nylon housing: ABS plastic |
| Can be used in EX zone | zones 0, 1 or 2 division 1 or 2 (when connected via separator) |
| Detectable gases (depending on the version) | 0 ... 25 vol% O2 (oxygen) 0 ... 500 ppm CO (carbon monoxide) 0 ... 50 ppm H2S (hydrogen sulfide) 0 ... 2 ppm PH3 (phosphane) Other gases on request. Please use our questionnaire for this. |
| Protection class | IP 65 |
| Signal output | 2-wire 4...20 mA output |
| Cable inputs | M20 |
| Approval | ATEX, IECEx II 1 G Exia IIC T4 Ga UL- & cUL-Class I Groups A,B,C,D |
| EMC compliance | EN 50270 FCC ICES-003 |
| Repeatability | ±2% FSD (typical value) |
| Operating voltage | 8...32 V DC 4-20 mA current loop powered |
| Temperature range | -10 ... +55 °C / 14 ... 131 °F |
| Humidity | 15 ... 90% RH |
| Dimensions | 160 x 123 x 92 mm / 6.3 x 4.8 x 3.6" |
| Weight | 0.7 kg / 1.5 lb |