The Isolation Meter PCE-IT100 detects, with auxiliary voltages of 125V, 250V, 500V and 1000V, insulation resistances up to a maximum of 4000 MΩ. Furthermore, the measurement of low-resistance resistors up to 400 Ω and a measurement function for alternating and DC voltages are offered by this Isolation Meter. A continuity tester with a beep is also part of the equipment of the insulation meter. In addition to a data-hold function for holding the current measured value, the max. or min. value in the Isolation Meter can also be recorded during voltage and low-ohm measurements.
Thanks to the large numbers and the lighting, the display of the Isolation Meter is easy to read even under difficult lighting conditions. The large buttons and the rotary knob for selecting the measuring functions allow easy operation of the PCE-IT 100 insulation meter. The Isolation Meter comes with a set of test leads with test probes, a test lead with a crocodile clip and 6 batteries.
- For new plants (dry rooms): 1000 ohms x volts of operating voltage (e.g., at 230 volts > 230 kOhms)
- For new installations (wet rooms, outdoors): 500 ohms x volts of operating voltage
- Earthed devices: 1000 ohms x volts of operating voltage
- Protected devices: 2 MOhm
- Power tools: 2 MOhm
- Protective extra-low voltage: 250 kOhm
- Electrical measuring devices: 5 MOhm
- Common test voltage values are 100 volts for low-voltage and telecommunication systems, 500 volts for building installations and home appliances, and 1000 volts for low-voltage motors and transformers
| Direct voltage DC | |
| Measuring range | 0 ... 1000 V |
| Resolution | 1 V |
| Accuracy | ±(0.8% 3 Digits) |
| Overload | 1000 V rms |
| AC voltage | |
| Measuring range | 0 ... 750 V |
| Resolution | 1 V |
| Accuracy | ±1.2% ±10 Digits |
| Overload | 750 V rms |
| Frequency range | 40 ... 400 Hz |
| Insulation resistance | |
| Test voltage DC | 125V |
| Measuring range | 0,125 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) |
| Insulation resistance | |
| Test voltage DC | 250V |
| Measuring range | 0,25 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) M Ω |
| Insulation resistance | |
| Test voltage DC | 500V |
| Measuring range | 0,5 ... 4000 M Ω |
| Resolution | 0,001 M Ω |
| Accuracy | ±(2% +10 Digits) |
| Insulation resistance | |
| Test voltage DC | 1000V |
| Measuring range | 1 ... 4000 M Ω |
| Resolution | 0,01 M Ω |
| Accuracy | ±(3% +10 Digits) |
| Resistance | |
| Measuring range | 0 ... 40 Ω |
| Resolution | 0,01 Ω |
| Accuracy | ±1.2% ±3 digits |
| Resistance | |
| Measuring range | 0 ... 400 Ω |
| Resolution | 0,1 Ω |
| Accuracy | ±1.2% ±3 digits |
| General technical data | |
| Measuring functions | MIN, MAX, HOLD |
| Measuring rate | 0,4 Hz |
| Automatic power-off | 10 min |
| Operating height | 2000 m max. above sea level |
| Test current | ≤ 200 mA |
| Fuse(s) | 10 A / 600V (5 x 20 mm) |
| Menu language | English, English (GB) |
| Protection class (device) | IP20 |
| (Rechargeable) battery | 6 x 1,5 V AA battery , Alkali-manganese |
| Capacity | 3000 mAh |
| Operating conditions | 0 ... 40 °C , 0 ... 80 % RH |
| Storage conditions | -10 ... 60 °C , 0 ... 70 % RH |
| Dimensions ( L x W x H ) | 200 x 92 x 50 mm |
| Weight | 700 g |